VS-616G5 Programming Manual
59
V/f
V/f w/PG Open Loop
Vector
Flux
Vector
E2
Motor Set-up
Sets the motor rated current in units of 0.01A for inverter models 27P5, 47P5 and smaller; 0.1A for
models G5U2011, G5U4011 and larger. The default setting varies depending on the inverter model set-
ting (O2-04).
Setting range:
0.00 to 20.00Hz
Sets the motor rated slip frequency in units of 0.01Hz. The default setting varies depending on the
inverter model setting (O2-04). Use the following equation to calculate the motor rated slip frequency:
Sets the motor no-load current in units of 0.01A for inverter models 27P5, 47P5 and smaller; 0.1A for
models G5U2011, G5U4011 and larger. The default setting varies depending on the inverter model set-
ting (O2-04).
Setting Range:
2 to 48 poles
Factory Default:
4 poles
Sets the number of motor poles.
Sets the motor phase-to-phase resistance value in units of 0.01W.
The default setting varies depending on the inverter model setting (O2-04).
E2-01 Motor Rated Current
Motor Rated FLA
Q
Q
Q
Q
E2-02 Motor Rated Slip Frequency
Motor Rated Slip
A
A
Q
Q
E2-03 Motor No-Load Current
No-Load Current
A
A
Q
Q
E2-04 Number of Motor Poles
Number of Poles
−
Q
−
Q
E2-05 Motor Terminal Resistance
Term Resistance
A
A
A
A
where:
f
s
f
N P
⋅
(
)
120
-----------------
–
=
f
s
: slip frequency (Hz)
f : rated frequency (Hz)
N : rated motor speed (rpm)
P : number of motor poles
Phase-to-Phase Resistance at
273 + (25ºC + insulation class temperature) / 2
273 + insulation class temperature
Motor Terminal Resistance = Insulation Class Temperature ×
Section E: Motor Parameters
E2 Motor 1 Set-up