11  Troubleshooting

SMA Solar Technology AG

70

WB3-5TL-21-IA-en-10

Installation Manual

11.3 Cleaning the Inverter

• If the cooling fins on the rear of the enclosure are dirty, clean them with a soft brush.
• If the air ducts on the top of the inverter are dirty, clean them with a soft brush.

8101 to
8104

Comm. disturbed

The cause must be determined by the SMA Service Line.
Corrective measures:

• Contact the SMA Service Line.

9002

Inst. code invalid

The SMA Grid Guard code entered is incorrect. The
parameters are still protected and cannot be changed.
Corrective measures:

• Enter the correct SMA Grid Guard code.

9003

Grid param. locked

The parameters are locked. The parameters cannot be
changed.
Corrective measures:

• Unlock the parameters with the SMA Grid Guard

code.

9005

Waiting for main CPU.
Ensure DC supply

DC supply is insufficient. The inverter was not able to
adopt the parameter change.
Corrective measures:

• Ensure that the rectifier is correctly connected (see

Section 6.4.3).

• Ensure that the small wind turbine system provides

sufficient DC voltage in windy conditions.

9007

Abort self-test

The self-test was stopped due to DC voltage being too
low.
Corrective measures:

• Wait for sufficient wind.

Damage to the display due to the use of cleaning agents

• If the inverter is dirty, clean the enclosure lid, the display, and the LEDs using only clean

water and a cloth.

Event
number

Display message

Cause and corrective measures