11 Troubleshooting
SMA Solar Technology AG
62
WB3-5TL-21-IA-en-10
Installation Manual
401
Grid fault
The inverter is no longer in grid-parallel operation.
The inverter has stopped feeding into the power
distribution grid.
Corrective measures:
• Check the grid connection for strong, short-term
frequency variations.
501
Grid fault
The power frequency is not within the permissible range.
The inverter has disconnected from the power distribution
grid.
Corrective measures:
• If possible, check the power frequency and observe
how often fluctuations occur.
If there is a high number of fluctuations and this
message is displayed frequently, contact the grid
operator and ask whether they approve a change
of the operating parameters of the inverter.
If the grid operator approves, discuss any changes
to the operating parameters with the SMA Service
Line.
601
Grid fault
The inverter has detected an excessively high proportion
of direct current in the line current.
Corrective measures:
• Check the grid connection for direct current.
• If this message is displayed frequently, contact the
grid operator and check whether it is possible to
raise the limiting value for monitoring on the
inverter.
Event
number
Display message
Cause and corrective measures