SMA WB 3000-21 Installation User Manual
Page 63

SMA Solar Technology AG
11 Troubleshooting
Installation Manual
WB3-5TL-21-IA-en-10
63
701
Frq. not permitted
Check parameter
The power frequency is not within the permissible range.
The inverter has disconnected from the power distribution
grid.
Corrective measures:
• If possible, check the power frequency and observe
how often fluctuations occur.
If there is a high number of fluctuations and this
message is displayed frequently, contact the grid
operator and ask whether they approve a change
of the operating parameters of the inverter.
If the grid operator approves, discuss any changes
to the operating parameters with the SMA Service
Line.
801
Waiting for grid voltage
Grid failure
Check fuse
The AC cable is not correctly connected or the country
data set is not correctly configured.
Corrective measures:
• Ensure that the AC cable is correctly connected
• Ensure that the country data set has been
configured correctly.
• Check fuse.
901
PE conn. missing
Check connection
PE not connected correctly
Corrective measures:
• Ensure that the PE is correctly connected
1001
L / N swapped
Check connection
The connection of L and N is swapped.
Corrective measures:
• Ensure that L and N are correctly connected
1101
Installation fault
Check connection
The connection of L and N is incorrect.
Corrective measures:
• Ensure that L and N are correctly connected
Event
number
Display message
Cause and corrective measures