11 Troubleshooting
Installation Manual
WB3-5TL-21-IA-en-10
69
7305
Update RS485i module
failed
Internal error. The inverter continues to feed into the
power distribution grid.
Corrective measures:
• Re-try update.
• If this message is displayed again, contact the
SMA Service Line.
7307
Update BT failed
Internal error. The inverter continues to feed into the
power distribution grid.
Corrective measures:
• Re-try update.
• If this message is displayed again, contact the
SMA Service Line.
7311
Update language table
failed
Internal error. The inverter continues to feed into the
power distribution grid.
Corrective measures:
• Re-try update.
• If this message is displayed again, contact the
SMA Service Line.
7401
Varistor defective
At least 1 of the thermally monitored varistors is defective.
Corrective measures:
• Check the function of the varistors
7508
External fan fault
The external fan is defective or blocked.
Corrective measures:
• Ensure that the fan is clean.
• Ensure that the external fan is correctly connected.
7701 to
7703
Self diagnosis
Interference device
The cause must be determined by the SMA Service Line.
Corrective measures:
• Contact the SMA Service Line.
8001
Derating occurred
The inverter has reduced its power output for more than
ten minutes due to excessive temperature.
Corrective measures:
• If this message is frequently displayed, clean the
cooling fins and air ducts (see Section 11.3).
• Ensure that the inverter has sufficient ventilation.