11 Troubleshooting
SMA Solar Technology AG
64
WB3-5TL-21-IA-en-10
Installation Manual
1501
Reconnection fault grid
The changed country data set or the value of a parameter
you have set does not correspond to the local
requirements. The inverter cannot connect to the power
distribution grid.
Corrective measures:
• Ensure that the country data set has been
configured correctly. Check the setting of the rotary
switches A and B or select the parameter
Set country standard or CntrySet and check the
value.
3301 to
3303
Unstable operation
The supply at the DC input is not sufficient for stable
operation. The inverter cannot connect to the power
distribution grid.
Corrective measures:
• Ensure that the small wind turbine system is
correctly rated.
3304
Gen. output too low
The small wind turbine system delivers insufficient DC
power. The inverter cannot connect to the power
distribution grid.
Corrective measures:
• Wait for stronger wind, if necessary reduce the
critical voltage to start feed-in. To do this, change
the parameter Critical voltage to start feed-in or
A.VStr.
• If this message is frequently displayed at medium
wind conditions, ensure that the small wind turbine
system is correctly rated.
Event
number
Display message
Cause and corrective measures