7 initial start-up, 1 procedure, 2 configuring the country data set – SMA WB 3000-21 Installation User Manual
Page 42: 1 procedure 7.2 configuring the country data set

7 Initial Start-Up
SMA Solar Technology AG
42
WB3-5TL-21-IA-en-10
Installation Manual
7 Initial Start-Up
7.1 Procedure
Before you can commission the inverter, you must check various settings and if necessary make
changes. This section describes the procedure for initial start-up and provides an overview of the steps
that must always be performed in the given sequence.
7.2 Configuring the Country Data Set
There is a display language assigned to each country data set. Configure the country data set with
the associated display language so it is appropriate for your country or purpose. If the display
language is not your desired language, you can change the display language after commissioning
(see Section 8.1).
1. Ensure that the inverter is disconnected from voltage sources and the lower enclosure lid is open.
Procedure
See
1. Check the country data set configuration of the inverter.
Type label or
supplementary sheet
with default settings
2. If the country data set is not correctly configured for your country or
purpose, adjust the desired country data set and the associated
display language.
Section 7.2
3. If the inverter will communicate with several Bluetooth devices, or if
Bluetooth will not be used as a type of communication, configure
NetID.
Section 7.3
4. Commission the inverter for the first time and start a self-test, if
required.
Country data set must be correctly configured
If you configure a country data set that is not valid for your country or purpose, it can cause a
disturbance in the plant and lead to problems with the grid operator. When selecting the
country data set always observe the locally valid standards and directives, as well as the
characteristics of the plant (e.g. dimensions of the plant, grid-connection point, etc.).
• If you are not sure which country data set is valid for your country or purpose, contact
your grid operator and ask which country data set should be configured.