beautypg.com

2 safety, 1 intended use – SMA SI 3.0-11 Quick Reference Guide V.3.0 User Manual

Page 7

background image

SMA Solar Technology AG

2  Safety

Installation - Quick Reference Guide

Ersatzstrom-IS-en-30

7

2 Safety

2.1 Intended Use

In the event of grid failure, a battery backup system with Sunny Island supplies loads with energy and a grid-tie PV system

with voltage. In the event of grid failure, an automatic transfer switch disconnects the battery backup grid from the utility

grid. After disconnection, the loads and the PV system have no supply for approximately five seconds, until the battery

backup system can provide active and reactive power once more. The battery backup system supplies the loads and the

PV system can synchronize with the battery backup grid and feed in.
The battery backup system should only be used in countries for which it is licensed or for which it is released by

SMA Solar Technology AG and the grid operator. To fulfill the technical connection requirements of the grid operator

and the local standards and directives, you must select one of the following basic structures:

• Battery backup system with all-pole disconnection

In the event of grid failure, a tie switch disconnects all line conductors and the neutral conductor from the utility grid.

The tie switch is designed with built-in redundancy. If the technical connection requirements of the grid operator or

the local standards and directives call for or allow all-pole disconnection, you must install this basic structure. You

must install all-pole disconnection in the following countries:

– Belgium
– Denmark
– Germany
– France
– Austria
– Switzerland

• Battery backup system without all-pole disconnection

In the event of grid failure, a tie switch disconnects all line conductors from the utility grid. The neutral conductor of

the battery backup grid remains permanently connected to the utility grid. If the technical connection requirements

of the grid operator or the local standards and directives prohibit disconnection of the neutral conductor, you must

install this basic structure. In Australia, you must install a battery backup system without all-pole disconnection.

Each basic structure can be designed either as a three-phase battery backup grid or as a single-phase battery backup

grid. Single-phase battery backup grids can be connected to three-phase utility grids.
In a three-phase battery backup system, in the event of grid failure, three Sunny Island inverters supply all line conductors

with the corresponding line conductor. The three Sunny Island inverters are connected in parallel on the DC side and form

one cluster. Only Sunny Island inverters of the same device type may be installed in a cluster. In a three-phase battery

backup system, both single-phase and three-phase PV inverters can be connected. Multiple clusters must not be connected

together.
In a single-phase battery backup system, in the event of grid failure, one Sunny Island supplies the battery backup grid.

A grid failure is only recognized at the line conductor which is connected to the Sunny Island. In the event of grid failure,

only single-phase PV inverters can feed in to a single-phase battery backup grid. A phase coupling, in the event of grid

failure, enables combination of the line conductors to a single-phase distribution grid. With phase coupling, all the loads

in the battery backup grid must be single-phase. No more than one Sunny Island may be connected in a single-phase

battery backup system.
A PV system can be connected in the battery backup grid. The PV system must be suitable for use in battery backup

systems (see the Planning Guidelines "SMA Flexible Storage System with Battery Backup Function" at

www.SMA-Solar.com). The power of the PV system must be appropriate for the system (see Section 3.2 "System

Information", page 12).
The automatic transfer switch is not a distribution board for the loads or the PV system. The loads and the PV system must

be secured with protective devices in accordance with the local standards and directives. Grid-forming voltage sources

(e.g., generators) must not be connected.

This manual is related to the following products: