beautypg.com

SMA SI 3.0-11 Quick Reference Guide V.3.0 User Manual

Page 42

background image

7  Commissioning

SMA Solar Technology AG

42

Ersatzstrom-IS-en-30

Installation - Quick Reference Guide

Set the battery type.

LiIon_Ext-BMS: lithium-ion battery

VRLA: lead-acid battery with electrolyte absorbed in glass

mat or immobilized in gel

FLA: lead-acid battery with liquid electrolyte

Set the battery capacity for ten-hour electric discharge

(for determining the battery capacity, see the Sunny Island

inverter installation manual).

Set the nominal voltage of the battery.

Set the battery capacity for ten-hour electric discharge

(for determining the battery capacity, see the Sunny Island

inverter installation manual).

Also, during the first ten operating hours, set the country data set:

AR-N4105: configuration in accordance with the application rule VDE-AR-N 4105

AS4777: configuration in accordance with the standard AS4777

Set increased self-consumption:

BackupOnly: system without increased self-consumption

SelfConsBackup: system with increased self-consumption

This manual is related to the following products: