SMA Solar Technology AG

4  Battery Backup Systems With All-Pole Disconnection

Installation - Quick Reference Guide

Ersatzstrom-IS-en-30

27

G

Control cable of the tie

switch

Sunny Island: connection Relay1 terminals C and NC
Automatic transfer switch: connection X4 terminals 1 and 2
If the multifunction relay activates, the contactors of the tie switch

deactivate.
Conductor cross-section: 1.5 mm² to 2.5 mm²

H

Control cable of contactor

Q4

Sunny Island: connection Relay2 terminals C and NO
Automatic transfer switch: connection X5 terminals 1 and 2
If the multifunction relay activates, contactor Q4 activates.
Conductor cross-section: 1.5 mm² to 2.5 mm²

I

Measuring cable for

monitoring the tie switch

Sunny Island: connections DigIn+ and BatVtgOut+
Automatic transfer switch: connection X5 terminals 3 and 4
Inside the Sunny Island inverter, connect connections DigIn − and

BatVtgOut − .
Conductor cross-section: 0.2 mm² to 2.5 mm²

K

Data cable to

Sunny Remote Control

Sunny Island: Display connection

L

Speedwire network cable

Sunny Island: ComETH connection
In order to connect the router/network switch, the Speedwire data module

Sunny Island must be mounted in the Sunny Island (see Sunny Island

Speedwire data module installation manual). The ComETH connection is

on the data module.

M

Data cable for battery

management

Sunny Island: ComSync In connection
You only have to connect a data cable to the battery if lithium-ion batteries

are used. The communication bus must be equipped with a terminator on

both ends.

N

Data cable for the internal

communication in the cluster

Sunny Island: ComSync Out connection
Connection of internal communication bus of slave 1

Position

Designation

Description/information