4  Battery Backup Systems With All-Pole Disconnection

SMA Solar Technology AG

26

Ersatzstrom-IS-en-30

Installation - Quick Reference Guide

4.2.3 Connecting the Master

Figure 8: Connecting the master

Position

Designation

Description/information

A

Cable for the control voltage Sunny Island: connection AC1 Loads/SunnyBoys terminals L and N

Automatic transfer switch: connection X5 terminals L and N
Conductor cross-section: 2.5 mm² to 16 mm²

B

AC power cable

Sunny Island: connection AC2 Gen/Grid terminals L, N

TT

,

and PE

Automatic transfer switch: connection X3 terminals L1, N, and PE
Conductor cross-section: 10 mm² to 16 mm²

C

Measuring cable for voltage

measurement

Sunny Island: connection ExtVtg terminals L and N
Automatic transfer switch: connection X4 terminals L1 and N
Conductor cross-section: 1.5 mm² to 2.5 mm²

D

DC+ cable

Battery connection
Conductor cross-section: 50 mm² to 95 mm²
Cable diameter: 14 mm to 25 mm

E

DC − cable

F

Measuring cable of the

battery temperature sensor

Sunny Island: BatTmp connection
You only have to connect a battery temperature sensor if lead-acid

batteries are used.
Mount the battery temperature sensor in the middle of the battery

connection, in the upper third of the battery cell.