6  Maintenance under Voltage-Free Conditions

SMA Solar Technology AG

28

SCCP-JP-WA-A4-en-12

Maintenance Manual

☐ Abrasive cloth
☐ Degreaser

Procedure:

2. Open the inverter doors.
3. Remove dirt.
4. To remove small-area surface damage:

• Sand the surface.
• Clean the surface with degreaser.
• Paint the surface.

5. To remove large-area surface damage:

• Sand the surface.
• Clean the surface with degreaser.
• Paint the entire surface.

6.6 Mounting the Panels

2. Mount the protective covers.
3. Fasten the grounding conductors to the panels of the interface cabinet. Torque: 8 Nm
4. Ensure that the grounding straps are firmly in place.
5. Fasten the panels using screws.

1.

'$1*(5

Danger to life due to electric shock or electric arc by touching live components

• Switch off the inverter and wait at least 15 minutes it, until the capacitors have discharged completely.
• Disconnect the inverter (see Section 6.1).

1.

'$1*(5

Danger to life due to electric shock or electric arc by touching live components

• Switch off the inverter and wait at least 15 minutes it, until the capacitors have discharged completely.
• Disconnect the inverter (see Section 6.1).