SMA SC 500CP-10-JP Maintenance Manual User Manual
Page 25
SMA Solar Technology AG
6 Maintenance under Voltage-Free Conditions
Maintenance Manual
SCCP-JP-WA-A4-en-12
25
Labels on the Silencing Baffle
Figure 6: Position of the labels on the silencing baffle
Procedure:
2. Open the inverter doors.
3. Check whether any warning message or label is damaged or missing.
Replace the warning messages and labels if they are missing or illegible. If necessary, you can order the labels from
SMA Solar Technology AG or your distributor under the SMA order number stated above.
F
86-1086701025
Risk of burns due to hot fuses under the cover
G
86-0043553
Risk of electric shock from active power source
H
86-003307
Five safety rules
I
86-1086701026
The negative terminal in the PV array is grounded in the inverter.
86-1086701027
The positive terminal of the PV array is grounded in the inverter.
K
86-003304
Inadvertent tripping due to modified settings
L
86-003306
PV system protected by surge arresters
M
86-1086701023
Risk of electric shock from active power source
N
86-003305
Wrong connection will destroy the device
O
86-0099
Position of grounding
P
86-1086701024
Risk of burns due to hot components under the cover
Q
86-10867153
Dangerous touch voltage even when device is disconnected
Position SMA order number
Designation
A
86-101500.01
Beware of hot surface
1.
'$1*(5
Danger to life due to electric shock or electric arc by touching live components
• Switch off the inverter and wait at least 15 minutes it, until the capacitors have discharged completely.
• Disconnect the inverter (see Section 6.1).
Position SMA order number
Designation