beautypg.com

3 cleaning the ventilation, 1 cleaning the ventilation plate, 2 cleaning the air duct and ventilation grids – SMA SC 500CP-10-JP Maintenance Manual User Manual

Page 19

background image

SMA Solar Technology AG

6  Maintenance under Voltage-Free Conditions

Maintenance Manual

SCCP-JP-WA-A4-en-12

19

6.3 Cleaning the Ventilation

6.3.1 Cleaning the Ventilation Plate

2. Remove the panels (see Section 6.2).
3. Pull the ventilation plate out of the inverter cabinet. To do this, grip

the ventilation plate from underneath and press upwards in the

middle.

4. Clean the ventilation plate with a brush or vacuum.
5. Slide the ventilation plate into the inverter cabinet. The ventilation

grid in the ventilation plate must face the rear panel.

☑ The ventilation grid is flush with the inverter enclosure.

✖ The ventilation plate will not go all the way in?

• Grasp the ventilation plate from underneath and press the

middle part upwards while sliding it in.

6.3.2 Cleaning the Air Duct and Ventilation Grids

2. Release the screws of the right-hand ventilation grid.

3. Pull the lower side of the right-hand ventilation grid forwards to

remove it.

1.

'$1*(5

Danger to life due to electric shock or electric arc by touching live components

• Switch off the inverter and wait at least 15 minutes it, until the capacitors have discharged completely.
• Disconnect the inverter (see Section 6.1).

1.

'$1*(5

Danger to life due to electric shock or electric arc by touching live components

• Switch off the inverter and wait at least 15 minutes it, until the capacitors have discharged completely.
• Disconnect the inverter (see Section 6.1).