6  Maintenance under Voltage-Free Conditions

SMA Solar Technology AG

20

SCCP-JP-WA-A4-en-12

Maintenance Manual

4. Release the screws of the left-hand ventilation grid.

5. Pull the lower side of the left-hand ventilation grid forwards to

remove it.

6. Vacuum the air duct from the outside or clean it with a brush.

7. Vacuum the ventilation grids or clean them with a brush.
8. Check the ventilation grids for visible damage.

☑ The ventilation grids are not damaged.

✖ The ventilation grids are damaged?

• Replace damaged ventilation grids.

9. Insert the right-hand ventilation grid.

10. Screw the right-hand ventilation grid on (torque: 20 Nm).