beautypg.com

2 checking the latches, door stops and hinges, 3 checking the surface of the switch cabinet, 4 checking the switch cabinet for corrosion – SMA SC 500CP-10-JP Maintenance Manual User Manual

Page 27

background image

SMA Solar Technology AG

6  Maintenance under Voltage-Free Conditions

Maintenance Manual

SCCP-JP-WA-A4-en-12

27

6.5.2 Checking the Latches, Door Stops and Hinges

Required maintenance material (not included in the scope of delivery):

☐ A suitable, water-free and heat-resistant lubricant, e.g. WD40
☐ Non-lubricating antifreeze agent (e.g. PS88)

Procedure:

2. Check that the doors latch easily. Open and close the doors several times.

If the doors do not latch easily, lubricate all moving parts of the latch.

3. Check whether the doors are arrested.

If the doors are not arrested, lubricate the door stops.

4. Check whether the door hinges move easily.

If the door hinges do not move easily, lubricate them.

5. Lubricate all moving parts and movement points.
6. Tighten any loose screws with the corresponding torque.
7. If the inverter is installed in regions where below-freezing temperatures occur, apply the non-greasing antifreeze to

the profile cylinder of the door lock and the key switch in order to protect against freezing.

6.5.3 Checking the Surface of the Switch Cabinet

2. Check surfaces for damage or corrosion.

If the surfaces are damaged or corroded, repair them without delay or within three weeks at the latest.

6.5.4 Checking the Switch Cabinet for Corrosion

Required maintenance material (not included in the scope of delivery):

☐ Use touch-up sticks, paint brushes, cans of spray paint or, alternatively, 2K-PUR acrylic paint in the appropriate

RAL color to repair small-area surface damage. Observe the relevant instructions of the paint manufacturer.

☐ Use touch-up paint or alternatively 2K-PUR acrylic paint in the appropriate RAL color to repair large-area surface

damage. Observe the relevant instructions of the paint manufacturer.

1.

'$1*(5

Danger to life due to electric shock or electric arc by touching live components

• Switch off the inverter and wait at least 15 minutes it, until the capacitors have discharged completely.
• Disconnect the inverter (see Section 6.1).

1.

'$1*(5

Danger to life due to electric shock or electric arc by touching live components

• Switch off the inverter and wait at least 15 minutes it, until the capacitors have discharged completely.
• Disconnect the inverter (see Section 6.1).

Position

RAL color

Shade

Roof

RAL 7004

Signal gray

Base

RAL 7004

Signal gray

Enclosure

RAL 9016

Traffic white

Silencing baffle*

* optional

RAL 7035

Light gray