6.4.3 Checking the Surge Arrester

Figure 4: Position of the overvoltage protectors

Additionally required maintenance material (not included in the scope of delivery):

☐ A surge arrester testing device approved by the manufacturer of the surge arrester such as the PM20 by

DEHN + SÖHNE GmbH + Co. KG.

Procedure:

2. Open the inverter doors.
3. Check if ready indicators are tripped.

If ready indicators are tripped, replace surge arresters.

4. Use the testing device to check that the surge arresters are operational (instructions for testing are included in the

testing device user manual).
If surge arresters are defective, replace them.

Position

Designation

A

Surge arrester

1.

'$1*(5

Danger to life due to electric shock or electric arc by touching live components

• Switch off the inverter and wait at least 15 minutes it, until the capacitors have discharged completely.
• Disconnect the inverter (see Section 6.1).