4 Maintenance Intervals
Maintenance Manual
SCCP-JP-WA-A4-en-12
13
4 Maintenance Intervals
Maintenance under normal ambient and operating conditions:
Preventive replacement intervals:
Spare Parts
Spare parts can be identified via their reference designation and the circuit diagram. The spare parts list includes the
article numbers of each spare part. For information on a specific article number, contact the SMA Service Line.
Shorter maintenance intervals in the event of adverse ambient conditions
The location of the PV system and ambient conditions influence the maintenance intervals.
• If the inverter is installed in adverse ambient conditions, SMA recommends a monthly inspection in order to
determine the need for maintenance. The maintenance intervals are to be shortened depending on the
determined maintenance requirements. In particular, cleaning work and corrosion protection may be necessary
more frequently.
• Adherence to the maintenance intervals ensures trouble-free operation of the inverter (see the maintenance
report of the inverter).
Description
Interval
Routine maintenance
Every 24 months
Description
Interval
Replacement of 24 V power supply units*
* Contact the SMA Service Line.
Every ten years
Replacement of inverter bridge fan*
Every 13 years**
** For option "Q at Night", the replacement intervals are halved.
Every 13 years**
GFDI / ABB high-performance circuit breaker*
After 100 trippings due to short circuit or after 7,000
switching cycles***
*** The trippings and switching cycles are recorded as instantaneous values (see Section 5.1 "Reading off the Replacement Interval Meter",
Remote Switch Unit of the GFDI*
After 7,000 switching cycles***
GFDI auxiliary signal contact*
Every six years
Surge arrester
If tripped
Key switch
In case of severe signs of wear
Label on the enclosure
If illegible, defective or missing