Temperature and humidity

Maintain appropriate temperature and humidity in the equipment room.

Lasting high relative humidity can cause poor insulation, electricity creepage, mechanical property
change of materials, and metal corrosion.

Lasting low relative humidity can cause washer contraction and ESD and bring problems including
loose captive screws and circuit failure.

High temperature can accelerate the aging of insulation materials and significantly lower the
reliability and lifespan of the firewall.

Table 1 Temperature and humidity requirements

Ambient temperature

Ambient relative humidity

Operating

0°C to 45°C (32°F to 113°F)

Nonoperating and storage

–40°C to +70°C (–40°F to +158°F)

Operating
10% to 95%, noncondensing

Nonoperating and storage

5% to 95%, noncondensing

Cleanness

Dust buildup on the chassis may result in electrostatic adsorption, which causes poor contact of metal
components and contact points, especially when indoor relative humidity is low. In the worst case,
electrostatic adsorption can cause communication failure.

Table 2 Dust concentration limit in the equipment room

Substance

Concentration limit (particles/cu m)

Dust particles

≤ 3 x 10

4

(No visible dust on desk in three days)

NOTE:

Dust particle diameter ≥ 5 μm

The equipment room must also meet strict limits on salts, acids, and sulfides to eliminate corrosion and
premature aging of components, as shown in

Table 3

.

Table 3 Harmful gas limits in an equipment room

Gas Max.

(mg/m

3

)

SO

2

0.2

H

2

S 0.006

NH

3

0.05

Cl

2

0.01