AEC HE Mass Flow Series Drying hoppers User Manual
Page 33

Page 32
HE
• CHE • BCHE Mass Flow Series Drying Hoppers
11. Slide the control chassis back into the control housing. The remaining parameters are set
with the keypad.
12. Prepare your unit for startup with a real or simulated load. Restore electrical power.
Figure 11
1/4 DIN Temperature Controller Preset Parameters
Parameter
setting levels
Parameter
description
PV LED
display
TDH SV LED
setting
0
Display at power-up.
Process
temperature
Process
set point
Alarm range.
25
°F
Proportional bandwidth.
39
°F
Reset time.
109 seconds
Rate time.
27 seconds
1
Lower limit value of control range.
0
°F
Upper limit value of control range.
400
°F
Heating control period.
20 seconds
Shift set value.
0
°F
2
Control output variable.
Read only.
Temperature sensor type.
Alarm mode.
Unit number setting w/optional
communications.
Varies with
network.
Baud rate setting w/optional
communications.
Varies with
network.