Installing the VDR24 Controller

36

VDR24 Radar Detection System, Rev 1.0

5.4.2. Health Outputs
Two isolated, normally open contacts (one for each radar’s health signal) are provided. When

these contacts are closed radar health is known to be good, based on internal self-check

procedures that run continuously every sixteen seconds. When contacts open, health is deemed

to be unsatisfactory or unknown. Internally this causes the VDR24 to revert to a failsafe state,

with all detection outputs forced in to a failsafe, presumptive ‘presence’ state. These signals are

also intended to be utilized by other railroad equipment which is configured to respond to

potentially failed or uncertain status of the radar detection system. To utilize these health

outputs, connect system Battery+ and a solid state or mechanical relay contact from the

equipment being controlled, in a high side or low side configuration, to the Health+ and Health-

outputs and to Battery -.
VDR24 outputs for health status connect to railroad equipment in the same manner as zone

detection outputs, shown above. Like the Zone outputs, each Health output channel can control

up to 200mA of current.