WCC3.EXE SCREEN DESCRIPTIONS
WCC III Technical Guide
3-88
Sat #:
Twenty satellites will appear on each Satellite Summary Screen.
If your system has more than twenty satellites, to view the next
twenty satellites, simply press
(Page Down) located on
the keypad to the right of the keyboard. To view the previous
twenty satellites, simply press
(Page Up) also located on
the keypad.
When fi rst entering this Satellite Summary Screen, you will
experience a slight delay in acquiring information on the screen.
This is because the system request needs to travel the entire
communication loop to gather the information needed for this
particular segment of the program.
Location:
This location is a user entered message which may pertain to the
name of the satellite, the location of the satellite, etc.
Satellite
Summary
Time
Date
Sat #
Location
Power-Up
Alarms
LOC TST
11:54 1/20
Delay
by-class
TYPE VER
ERR
1 S1-KC
5 Seconds 12345678
3
2.15 3 R
11:15 12/09/08
2
15 Seconds 12345678
3
2.14 5 R
13:46 09/22/08
3 KC Linux Test
20 Seconds 12345678
3
2.14 15 R 13:46 09/22/08
4 Bldg.#1 B.J. S240 10 Seconds 12345678
3.5 2.14 15 R 13:46 09/22/08
5 Non-Existent
6 Non-Existent
7 Non-Existent
8 Test Sat3D.5
2 Minutes 12345678
3D.5 2.14 4 R
14:22 09/22/08
9 Test Sat3D.5
2 Minutes 12345678
3D.5 2.14 4 R
14:22 09/22/08
10 Test Sat3D.5
2 Minutes 12345678
3D.5 2.14 4 R
14:22 09/22/08
11 Test Sat3D.5
2 Minutes 12345678
3D.5 2.14 4
R 14:22
09/22/08
12 Non-Existent
13 Non-Existent
14 Non-Existent
15 Non-Existent
16 Satellite #16
2 Minutes 12345678
3C
2.14 5 R
14:09 09/22/08
17 Satellite #17
2 Minutes 12345678
3C
2.14 5 R
14:09 09/22/08
18 Satellite #18
2 Minutes 12345678 3C
2.14
5
R
14:09
09/22/08
19 Satellite #19
2 Minutes 12345678
3C
2.14 5 R
14:09 09/22/08
20 Satellite #20
2 Minutes 12345678
3C
2.14 5 R
14:09 09/22/08
HOME for menu
SATELLITE SUMMARY SCREEN
Satellite Summary Screen
Power-Up Delay:
This feature allows the WCC III system to soft-start a building after
a main power failure. If power is lost to the building, the satellites
cannot control any of the equipment because everything will be
off. When power is restored, the binary output contacts on the
satellite controller will remain open for the power up delay time,
thus holding the equipment off. You may want to bring on a critical
satellite fi rst (lighting) and less critical satellites later.
Caution:
Please note that the contacts in the SATELLITE
will remain open during the power up delay time. This should
be taken into consideration when you are deciding whether an
open contact in the satellite should cause the equipment to be
ON or OFF.