WCC3.EXE SCREEN DESCRIPTIONS
WCC III Technical Guide
3-12
An analog input is a signal sent to the satellite controller that can 
be represented by a number such as temperature, pressure, etc. 
The Analog Input Screen is used to “tell” the WCC III system the 
characteristics of the sensor and to set alarm limits. The “Binary 
Setpoint” option at the bottom of the Analog Input Screen can be 
used to convert the analog input to a binary (On/Off) input.
Analog Inputs
Specifi es the summary type to be displayed. Because this is a 
“choice” fi eld, the list of available choices will be displayed at the 
bottom of the screen:
Trend Logging, Logic Switch, Binary Output> You can access one of the screens which appear in this choice fi eld    until the desired summary type has been selected and then pressing  . Satellite______ Specifi es the number of the satellite which you are currently  . 1 to 239. To view or edit a specifi c analog input, use the arrow keys to move  . The Analog Input Screen for  the specifi ed point will now appear. Time / Date The present time and date will automatically appear at these  Description:_______________ The description message which was entered on the Analog Input   ANALOG INPUT SUMMARY SCREEN -----------------------------------------------------------------------------------------     Analog Inputs  Satellite 1 S1-KC         Time Date  Analog  Inputs 08:22    01/20 Description  Current Value  Alarm Limits Stat Mode  Alarm Details A1: S1-A1  50.0 Deg F  65.0 80.0  ON A2: S1-A2  0 Deg F  45.0 65.0  OFF A3: S1-A3  0 Deg F -10.0 100.0  ON A4: S1-A4  0 Deg F  45.0 100.0  ON A5: S1-A5 C1:   OFF C2:   OFF C3:    OFF C4:   OFF C5: OFF HOME for menu Analog Input Screen’s WCC III Logical Address is XXXAY, where XXX = Satellite Address, A = Analog Input, and Y = 1-8 Analog Input Summary Screen
without returning to the Main Menu by pressing the 
communicating with. If you would like to view the analog input 
summary data for a different satellite, use the arrow keys to move 
the cursor to this fi eld, enter the desired satellite number, and press 
the cursor (shown as “>” along the left-hand side of the screen) to 
the desired point and press 
locations.
Screen is displayed here to help you identify the different analog 
inputs within the system.
A6: S1-A6
A7: S1-A7 9.0 Deg F
A8: S1-A8 99.0 Deg F
C6: OFF
C7: OFF
C8: OFF