Wcc3.exe screen descriptions, Global analog - integral mode average mode screen, Analog global integral mode average mode screen – WattMaster WCC III part 4 User Manual
Page 139

WCC III Technical Guide
3-135
WCC3.EXE SCREEN DESCRIPTIONS
Sampling From:
The value of the global analog will be the average of this input over 
the specifi ed time period.
For example, if 1A3 is input here, the system will periodically read 
the value of analog input #3 on satellite controller #1. The value 
of the global analog will be the average of the readings over the 
specifi ed time period.
Automatically reset by GBXXX being ON
This allows you to have the system automatically restart the 
averaging cycle when a global binary value goes either ON or 
OFF.
Because this second fi eld is a “choice” fi eld, the list of available 
choices will be displayed at the bottom of the screen:
GLOBAL ANALOG - INTEGRAL MODE
AVERAGE MODE SCREEN
ANALOG
Global
#:
30
Name
is
GA30
Description: AVG OA TEMP
Data Pattern: x,xxx
Unit
of
Measure:
1
°F
In Local Set this global defaults to LAST VALUE
 Mode 
3:
Integral
Sampling from : 1A3
Automatic Reset by GB1 being ON
Sampling rate:
1 Minutes
Window: 33 days
Mode:
Average
Divisor:
1
i
=
n
Global value =
(  (Di/n ) / divisor
i
=
1
If sampling data is unavailable, then use 50 as default value
---------------Alarm---------------
Range Low Limit High Limit
Type Message #
Message
None
Reset random data by pressing Ctrl-R after editing.
HOME for menu
Make your selection by pressing the
once for each
choice until the desired mode type has been selected, and then 
press 
.
Sampling Rate: 1 Minutes
Window: 33 Days
Assume we are monitoring outside air temperature and 1 minute 
is entered as the “sampling rate” and 33 days for the Window. The 
system will read the value of the outside air temperature every 
minute and then average the values until 33 days have elapsed. 
After 33 days the calculation process will start over.
In the example above, GB1 goes on at the beginning of each new 
month to restart the averaging process, so the end of the window is 
never reached. If the end of the window is reached, the system will 
restart the calculation process.
The sampling rate can vary from 1 minute to 99 hours. The window 
will accept from 0-9999 minutes, hours, days, or samples.
Analog Global Screen’s WCC III Logical Address is GAXXX, where GA = Global Analog and XXX = Global Analog Address
Analog Global Integral Mode Average Mode Screen
