WCC3.EXE SCREEN DESCRIPTIONS
WCC III Technical Guide
3-128
The term local set means that communication is lost between
the MCD and the satellite controllers. If the MCD stops
communicating, the global analog values will be gone. This
input allows you to specify a default value for the global
analog if the MCD quits communicating. You may input a fi xed
number, or you may choose to select LAST VALUE. If LAST
VALUE is chosen, the global analog will default to the value it
had when communications with the MCD were lost.
Mode
Because this is a “choice” fi eld, the list of available choices will
be displayed at the bottom of the screen:
External, Dual Valve, Proportion, Dual Ramp, Multi-Proportion, Pulse Start> Make your selection by pressing the once for each choice until the desired mode type has been selected, and then press . One of the following screens will appear, depending on which choice you select: Averaged List Math Function Sorted List Look-Up Table Integral External Sliding Window Dual Valve Average Proportion Accumulation Dual Ramp Multi-Proportion Pulse Start CAUTION: Select the mode before entering any other data on an Analog Global Screen. If other information is entered before the mode is selected, there is a chance that the global analog will not perform properly. If data has already been entered and you want to change the mode, you must fi rst clear the screen by using the feature, and then exit to the Global Analog Summary Screen before re-entering data. Analog Global Screen