Wcc3.exe screen descriptions, Analog input summary screen – WattMaster WCC III part 4 User Manual
Page 17
WCC III Technical Guide
3-13
WCC3.EXE SCREEN DESCRIPTIONS
Current Value
The current value of the analog input is automatically displayed
here.
Alarm Limits
The alarm limits which were input on the Analog Input Screens
will automatically be displayed here.
Stat
The present “ON” or “OFF” status of the binary input which is
controlling the schedule for the alarm limits is shown here. For
example, if week schedule #1 (W1) has been input to control
the schedule of the alarm limits, the message “ON” will appear
here when week schedule #1 is “ON” and “OFF” will appear
when week schedule #1 is “OFF”. When W1 is “ON” the “On
Schedule” alarm limits will be active, and when W1 if “OFF” the
Off Schedule” alarm limits will be active.
Mode
The “alt” message will appear here when the alternate alarm limits
are active. When the input value which has been entered on the
Analog Input Screen to select the alternate alarm limits is “ON,”
the WCC III system will use the “Alternate Alarm Limits” and the
“alt” message will be displayed here.
Alarm Details
This location will automatically display the alarm message, the
high or low value of the analog input, and the time and date of the
occurrence of the peak value.
When an alarm occurs, the alarm message will blink on the screen.
To acknowledge an alarm, position the cursor at the point for
which you wish to acknowledge the alarm. Then press
or left-click on
to bring up the
menu at which
point you can select
or
All Alarms>
.
NOTE:
The
option will
only work on the Alarm Summary Screen.
At this point, one of two things should happen. If the value of
the analog input is presently within the alarm limits, the message
will disappear. If the value of the analog input is not within the
alarm limits, the message will stay on the screen, but it will quit
blinking.
Analog Input Summary Screen