beautypg.com

Thermon TraceNet TCM 18 User Manual

Page 92

background image

Water

Product Maintenance Temperature:

50

F (10

C)

Product Freeze Point:

32

F (0

C)

Heater Cable Type:

Self Regulating Parallel Cable

Number of Circuits:

Ten Ambient Sensing

50% Caustic

Product Maintenance Temperature:

80

F (27

C)

Product Freeze Point:

54

F (12

C)

Heater Cable Type:

Self Regulating Parallel Cable

Maximum Caustic Temperature:

100

F (38

C)

Number of Circuits:

Eight Process Sensing

The TCM18 control module could be typically set as indicated below:

Control Parameter

Setting

Controller Configuration

1 AMB/ 1 or 2 RTD Inputs

Control Method

On-Off

Water Circuits

Maintain Temperature

50

F (10

C)

Control Band

5

F (3

C)

High Alarm Temperature

120

F (49

C)

High Temperature Trip

Off

Low Alarm Temperature

40

F (5

C)

Caustic Circuits

Maintain Temperature

80

F (27

C)

Control Band

5

F (3

C)

High Alarm Temperature

90

F (3

C)

High Temperature Trip

On

Low Alarm Temperature

60

F (15

C)

PN 50316_0514

88