beautypg.com

Thermon TraceNet TCM 18 User Manual

Page 30

background image

The second parameter line on this display screen
indicates the temperature units to be displayed on the
screen. Units to be displayed are either in degrees
Fahrenheit or degrees Celsius.

Note that these CONFIG settings are always global set-
tings for all eighteen circuits on this controller.

HEATER
ENABLE

Indicates the heat tracing circuit number displayed, the
heater circuit status (enabled, forced (on or off), dis-
abled (off), or tripped (off)), and the RTD setup (single
RTD pipe sense, dual RTD pipe sense, single RTD am-
bient sense, dual RTD ambient sense, or single RTD
on pipe or heater and single RTD ambient sensed.

DATA HWY

1

Indicates the data highway address for this TCM18
module, the programmed communication protocol, the
message type, and the communication Baud rate.

HIGH TEMP
ALARM

Indicates the heat tracing circuit number displayed and
the high temperature alarm and trip set points. If no trip
is set, the first and second level high temperature alarm
set points will be displayed.

LOW TEMP
ALARM

Indicates the heat tracing circuit number displayed and
the low temperature alarm set points.

HIGH CURRENT
ALARM

Indicates the heat tracing circuit number displayed and
the high heater operating current alarm and trip set
points. If no trip is set, the first and second level heater
current alarm set points will be displayed.

LOW CURRENT
ALARM

Indicates the heat tracing circuit number displayed and
the low heater operating current alarm set points.

(1, 2, 3, 4, 5)

Multiple presses of the applicable key or pressing ENTER on

the last screen entry will result in subsequent display screens appear-
ing.

PN 50316_0514

26