The TCM18 control module utilizing pipe sensing RTD’s could be typically set as
indicated below:

Control Parameter

Setting

Controller Configuration

Dual RTD Inputs

Control Method

Proportional

Maintain Temperature

80

F (27

C)

Control Band

5

F (3

C)

High Alarm Temperature

90

F (32

C)

High Temperature Trip

On

Low Alarm Temperature

60

F (15

C)

Power at Maintain Temp

100%

Considering that we have fifteen heat tracing circuits, the TCM18 would be set up
with 30 RTD sensors.

The heat tracing circuit control assignments would be as follows:

Circuit No.

Setting

1 thru 15

Enabled (2 Pipe)

16 thru 18

Spare

In this case power relays on circuits 16, 17, and 18 will not be connected to the heat
tracing and because the circuits are listed as “Spare” they will not appear during the
Scan Mode process.

Example D6 - Process Temperature and Ambient Sensing Control - Single and Dual
RTD Sensing

In many applications there are a variety of control applications. Some may be the
critical applications such as the 50% caustic in Example 5 and some may be simple
water freeze protection. For this combination application, the typical design require-
ments are as listed below: