beautypg.com

Thermon TraceNet TCM 18 User Manual

Page 8

background image

Current ratings in nonhazardous (ordinary) location based on TraceNet TC Series
panels for up to 72 circuits are as follows

1

:

Maximum Panel Exterior

Ambient (

C)

For: 1 - 36 Circuits

For: 37 - 72 Circuits

Maximum Allowable Average Amps per Relay

(Calculated for each side of enclosure)

2

20

27.0

22.7

25

25.8

21.6

30

24.7

20.4

35

23.5

19.2

40

22.2

18.0

45

21.0

16.8

50

19.7

15.6

55

18.3

14.3

Note 1: Contact the manufacturer for the maximum allowable amps per relay for custom enclosure sizes.

Note 2: Based on factory panel wiring rated for 105

C.

The TCM18 has the following operating specifications:

Rated supply voltage

100 to 240 Vac, 50/60 Hz

Display

4–7/8” (124 mm) x 1–3/4” (44 mm) LCD STN with LED
backlight

Touch pad

Membrane switch stainless steel dome tactile keys

Control capacity

Eighteen heat tracing circuits

Temperature inputs

Up to two 3 wire 100 Ohm Platinum RTD’s 32

F (0

C) per

heat trace circuit

Temperature control
range

-200

F to 1112

F (-129

C to 600

C)

Communication

Dual RS485 ports

Communication
protocol

ModBus ASCII or RTU

Communication rate

9600 to 57600 Baud

PN 50316_0514