Where the panel has external heat sinks to dissipate the heat generated by solid
state relay switching, it is recommended that a minimum of 6” (150 mm) of space
be allowed between sinks and walls or other panels to minimize heat buildup at the
heat sinks. Where heat sinks are present on adjacent panels, allow 12” (300 mm)
spacing between heat sinks for sufficient natural air movement.
Adequate door clearance for service work entry and conduit panel entries should be
anticipated when establishing the exact panel location. When the panel is located
outdoors, a concrete base pad of sufficient height to avoid potential standing water
should be constructed.
Once the panel has been properly located, refer to the project specific installation
details for the recommended floor mounting as well as wall mounting details.
Once bolted in place, the panel is ready for final configuration, wiring, and site re-
quired assembly. Note that the TCM18 control and monitoring module is normally
shipped in a separate container to minimize any undue impact stress during ship-
ment. It should be removed from its shipping container again being attentive to any
shipping damage that may have occurred during its transit. The TCM18 mounting
details are likewise provided in the project specific drawing details.
Note:
For installation requirements specific to purged panels, please see Appendix
F.