beautypg.com

Thermon TraceNet TCM 18 User Manual

Page 63

background image

given in the following table.

Tests

Description

Perform Self Test

The Self Test function (accessed by
pressing the CONFIG key) checks circuit
breaker and output relay functionality.

Perform SCAN Mode Review

Operator should do a visual check for out
of range temperatures and low or high
heater and ground/earth leakage current
in the heat tracing circuit(s). No alarms
shall be present on any circuits in the
fourth line of the display screen.

Perform Simulated Ground / Earth Leak-
age Trip Exercise

The

TCM18

can

simulate

a

high

ground/earth

leakage

(accessed

by

pressing the CONFIG key) and manually
cause a trip to occur.

This allows the

operator to verify that the ground/earth
leakage function is operable.

59

PN 50316_0514