Specifications

The general TraceNet TC Series panel specifications are as given below.

Interior panel operating ambient range

-40

F to 140

F (-40

C to 60

C)

Exterior panel operating ambient range

-40

F to 131

F (-40

C to 55

C)

Ambient storage range

-40

F to 158

F (-40

C to 70

C)

Relative humidity range

0 to 90% Non Condensing

Nominal instrument control voltage

100 to 240 Vac, 50/60 Hz

Temperature sensor types

100 Ohm 3 Wire Platinum RTD

Control temperature range

-200

F to 1112

F (-129

C to 600

C)

Maximum power consumption of TCM18 mod-
ule

70 Watts

Current ratings in hazardous (classified) locations based on TraceNet TC Series
panels for up to 72 circuits are as follows

1

:

Maximum Panel Exterior

Ambient (

C)

For: 1 - 36 Circuits

For: 37 - 72 Circuits

Maximum Allowable Average Amps per Relay

(Calculated for each side of enclosure)

2

40

22.2

18.0

45

21.0

16.8

50

19.7

15.6

55

18.3

14.3