System start-up – Thermon TraceNet TCM 18 User Manual

Page 58

background image

12

System Start-Up

All heat trace circuits should be properly terminated and meggered prior to energiz-
ing the heat trace power distribution and control panels. In addition, all pipes should
be insulated and weather sealed to achieve the expected heat up and temperature
maintenance performance of the system.

Troubleshooting Tips

When starting up a newly installed heat trace and control system, it is not uncom-
mon to encounter numerous alarm and trip events. Data entry errors, unanticipated
temperature overshoots due to system inertia or too tight control band settings, and
incomplete installation details are just a few of the many contributing factors to this
result. A table of Troubleshooting Tips is provided in Appendix A to assist during
start-up.