The TCM18 control module using foundation temperature sensing RTD’s in each
heating zone can be typically set at the control settings given below:

Control Parameter

Setting

Controller Configuration

Single RTD Input

Control Method

Proportional

100% Power On Temperature

50

F (10

C)

Control Band

30

F (17

C)

High Alarm Temperature

90

F (32

C)

High Temp Trip

On

Low Alarm Temperature

38

F (3

C)

In a proportional control mode, the heater should be continually operating using cy-
cle omission techniques in a warming mode (and will thus minimize condensation
within the heating system conduits). After attaining 50

F (10

C), the TCM18 will lin-

early reduce power until an equilibrium value between 50

F(10

C), and 80

F(27

C),

is obtained. In the unlikely event that the 80

F (27

C), setting is exceeded, the con-

trol will de-energize the heater circuit. A high temperature alarm will activate should
the RTD sensor detect a temperature above the 90

F (32

C) value and the circuit

will trip.

Having set in these values as well as the appropriate other limit/control values, the
following typical control can be achieved.