8 specifications – Sensoray 2600 User Manual
Page 53

2600 Family Instruction Manual
48
Chapter 8 : Model 2612 Strain Gauge/RTD Module
Command
(Adrs),(Data)
Response
none
Notes
This function is used by the middleware to store
calibration data for the module. Refer to the
distribution media for details.
Due to the lengthy time required to write a byte to
the EEPROM, this action should be invoked only
once per command packet.
8.8 Specifications
Parameter
Function
Adrs
Memory address that is to be written to.
Data
Byte value that is to be stored.
Table 25: Model 2612 Specifications
Analog Inputs
Resolution
24 bits
Input channels
4
Conversion rate
6.875 to 3500 samples/second for each channel.
Input range
±1/2 of reference.
Input impedance
110 kOhm, minimum, measured from either sensor input to reference voltage.
Power Outputs
Output channels
4
Output power
1.25V, 2V, 3V or 5V, ±10%@ 1 to 25 mA for each channel.
Mating Connectors
(*) = included with module
IOM port (qty 1)
RJ-45 plug, AMP 554169 or equivalent
Analog inputs (qty 4)
RJ-45 plug, AMP 554169 or equivalent
Analog inputs (qty 4)
(*)Pluggable TB, 8-pin, RIA 31166110 or equivalent
Temperature
Operating range
0 to 70°C
Power
Input power
+24V ±5% @ 60mA.
Dimensions
Outer dimensions
5.0H x 5.0W x 1.8D inches, including DIN mounting frame. Depth is specified with
respect to surface of DIN rail support panel; additional clearance required for field wiring.