beautypg.com

RLE LD1500 V.3.1 User Manual

Page 52

background image

52

LD1500 User Guide

800.518.1519

D

Technical Specifications

Protocols

TCP/IP, HTML, TFTP

IPv4.0; webpages comply with Rehabilitation Act of 1973,

sections 504 and 508, US Dept of Education (website

accessibility for computer users with disabilities)

SNMP

V1: V2C MIB-2 compliant; NMS Manageable with Get, Set,

Trap/Inform

Modbus (EIA-485)

Slave; RTU Mode; Supports function codes 03, 04, 06 and

16; Johnson N2

Modbus TCP/IP, UDP/IP

Modbus Slave; TCP/IP, UDP/IP transmission protocol

BACnet/IP

Conformance Level 1

BACnet (EIA-485)

Slave; MS/TP

Terminal Emulation (EIA-232)

VT100 compatible

Alarm Notification

Visual Alarm

Bi-color status LED

SNMP Traps (Ethernet)

2 Community Strings

Logging Capabilities

Event Log

Last 10 events

Login Security

Web Browser Access (Ethernet)

1 Web password Read Only; 1 Web password Read/Write

Terminal Emulation Access None

Front Panel Interface

LED Indicators

Power/Status: 1 bi-color (Power On: green; Alarm / Cable

Fault / Cable Contamination: red)

Operating Environment

Temperature

32° to 122°F (0° to 50°C)

Humidity

5% to 95% RH, non-condensing

Altitude

15,000ft (4,572m) max.

Storage Environment

-4° to 185°F (-20° to 85°C)

Dimensions

7.075"W x 3.625"H x 1.25"D (179.7mmW x 92.07mmH

x31.75mmD)

Weight

1.5 lbs. (680g)

Mounting

Vertical wall mount

Certifications

CE; ETL listed: conforms to UL 61010-1, EN 61010-1;

certified to CSA C22.2 NO. 61010-1; RoHS compliant

Table D.1 Technical Specifications (continued)