RLE LD1500 V.3.1 User Manual
Page 52
52
LD1500 User Guide
800.518.1519
D
Technical Specifications
Protocols
TCP/IP, HTML, TFTP
IPv4.0; webpages comply with Rehabilitation Act of 1973,
sections 504 and 508, US Dept of Education (website
accessibility for computer users with disabilities)
SNMP
V1: V2C MIB-2 compliant; NMS Manageable with Get, Set,
Trap/Inform
Modbus (EIA-485)
Slave; RTU Mode; Supports function codes 03, 04, 06 and
16; Johnson N2
Modbus TCP/IP, UDP/IP
Modbus Slave; TCP/IP, UDP/IP transmission protocol
BACnet/IP
Conformance Level 1
BACnet (EIA-485)
Slave; MS/TP
Terminal Emulation (EIA-232)
VT100 compatible
Alarm Notification
Visual Alarm
Bi-color status LED
SNMP Traps (Ethernet)
2 Community Strings
Logging Capabilities
Event Log
Last 10 events
Login Security
Web Browser Access (Ethernet)
1 Web password Read Only; 1 Web password Read/Write
Terminal Emulation Access None
Front Panel Interface
LED Indicators
Power/Status: 1 bi-color (Power On: green; Alarm / Cable
Fault / Cable Contamination: red)
Operating Environment
Temperature
32° to 122°F (0° to 50°C)
Humidity
5% to 95% RH, non-condensing
Altitude
15,000ft (4,572m) max.
Storage Environment
-4° to 185°F (-20° to 85°C)
Dimensions
7.075"W x 3.625"H x 1.25"D (179.7mmW x 92.07mmH
x31.75mmD)
Weight
1.5 lbs. (680g)
Mounting
Vertical wall mount
Certifications
CE; ETL listed: conforms to UL 61010-1, EN 61010-1;
certified to CSA C22.2 NO. 61010-1; RoHS compliant