LD1500 User Guide

27

4

Web Interface

Leak Alarm Delay

The amount of time that passes between the time a leak is detected

and the annunciation of the leak alarm.

The leak trip point must be exceeded for the duration of this delay.

Default setting: 20 seconds

Contamination

Alarm Delay

The amount of time that passes between the time a contamination

is detected and the annunciation of the contamination alarm.

The contamination trip point must be exceeded for the duration of

this delay.

Default setting: 120 seconds

Resistance Per Foot

The resistance per foot (or meter) of cable determines the

LD1500’s ability to accurately detect the cable length installed and

calculate distances to leaks. Adjust this value to fine-tune the

accuracy of a distance-read leak detection system.

RLE’s orange water sensing cable has a base resistance of 2.800

ohms per foot. Most other sensing cables, including RLE’s green

chemical-resistant sensing cable, have a base resistance of 4.000

ohms per foot. Consult the sensing cable’s datasheet for further

information.

The resistance value must be entered as a 4-digit number between

2.000 and 4.250, with one number in the tens place and three

numbers past the decimal point (x.xxx).

Default setting: 2.800 ohms per foot.

Measurement

Display

Select either feet or meters to calibrate the LD1500 to the preferred

unit of measure. All distance calculations will adjust accordingly.

Default setting: Feet

Option

Description

Table 4.1 Leak Configuration Options