4.3.8 BACnet

The LD1500 can communicate via BACnet. BACnet allows building automation and control

devices to communicate, regardless of the services they perform.

Before the LD1500 can communicate via BACnet MS/TP, you need to change the EIA/485

port function. This is done on the EIA-485/Modbus/N2 screen. Refer to “EIA-485/Modbus/

N2” on page 32.

You also need to set the EIA-485 slave (MAC) address. This allows the device to

communicate on the string. This is also done on the EIA-485/Modbus/N2 screen, highlighted

in “EIA-485/Modbus/N2” on page 32. Once this is complete, configure the remaining BACnet

communications paramers as follows:

Figure 4.12 BACnet Configuration Page

Option

Description

BACnet Device Name Designate a unique name for the LD1500, as it will appear on the

BACnet network.

BACnet Device ID

The unique identifier for the LD1500 on the BACnet network.

BACnet Description

The description of the LD1500 as it will appear on the BACnet

network.

BACnet UDP Port

This is the port to which the LD1500 will respond to BACnet

requests. The default number of zero in this field will configure the

LD1500 to listen on the standard BACnet port of 47808. See the

BACnet standard for more information.

BACnet MSTP Max

Master

Set the slave address, 1-127. 0 = slave only.

BACnet Information

Displays the status of the BACnet interface, including Alarm flag

status, BACnet Objects, BACnet Property Identifiers, and BACnet

Device Objects.

Table 4.6 BACnet Configuration Menu Options