4.3.7 EIA-485/Modbus/N2
If the LD1500 will communicate via the EIA-485 port, configure the necessary options here.
Figure 4.11 Modbus/EIA-485 Configuration Page
Option
Description
Modbus/TCP/UDP
Slave Unit Identifier
Specify the slave address used on the LD1500's IP port. This
designator is used for Modbus RTU over an Ethernet connection.
Set the slave unit identifier, 1-254. 0 = disabled.
Select EIA-485 Port
Function
Sets the EIA-485 port for Modbus-Slave, BACnet MS/TP-Slave, or
Modbus N2.
EIA-485 Slave
Address
Set the EIA-485 Port's slave address, 1-254. Each device on the
EIA-485 Modbus network must have a unique address.
EIA-485 Baud Rate
Sets the EIA-485 Port to 1200, 2400, 9600, 19200, or 38400 baud.
All the devices connected to the Modbus network must be set to
operate at the same Baud rate.
EIA-485 Parity
Sets the EIA-485 Port to None, Even or Odd Parity. All the devices
connected to the Modbus network must be set to operate at the
same parity.
Modbus Slave
Register Display
Displays the contents of the Modbus Slave Registers. See Table
5.3, “Output Registers” on page 39 and Table 5.5, “Input Registers”
on page 40 for descriptions of the register contents.
N2 Register Display
Log/Statistics
Displays the contents of the Modbus N2 registers and statistics.
Table 4.5 EIA-485/Modbus/N2 Menu Options