3.1.

Installing the LD1500

The LD1500 is a wall mounted device. There are four mounting holes on the sides of the unit

spaced 6.6 inches (.167m) apart. Use drywall anchors if securing the unit to drywall.

3.2.

Connecting the Leak Detection Cable

The LD1500 is shipped with a 15-foot (4.57m) leader cable. One end of this leader cable

connects to the LD1500 controller, and the other end connects to the SeaHawk sensing cable.

Connect each end of the leader cable as follows:

1

With the screws of the terminal block connector on the LD1500 facing up, connect the four

stripped, bare wires of the leader cable to the terminals in this order, from left to right:

white, black, green, red. Tighten the screws to secure the ends of the leader cable, and plug

the connector into TB2. Make sure the wires, from left to right, are in the white-black-

green-red order.

Note

If the terminal connector is removed from the end of the cable, make sure the wires are in

white-black-green-red order when the connector is reapplied.

2

Unscrew the end-of-line (EOL) terminator from the other end of the leader cable.

3

Attach the first length of leak detection cable (sensing cable) to the leader cable.

Figure 3.1 SeaHawk Sensing Cable