Installation, Installing the ld1500, Connecting the leak detection cable – RLE LD1500 V.3.1 User Manual
Page 17: Figure 3.1, Seahawk sensing cable, Nstallation
rletech.com
LD1500 User Guide
17
C
H A P T E R
C
HAPTER
0
I
NSTALLATION
3.1.
Installing the LD1500
The LD1500 is a wall mounted device. There are four mounting holes on the sides of the unit
spaced 6.6 inches (.167m) apart. Use drywall anchors if securing the unit to drywall.
3.2.
Connecting the Leak Detection Cable
The LD1500 is shipped with a 15-foot (4.57m) leader cable. One end of this leader cable
connects to the LD1500 controller, and the other end connects to the SeaHawk sensing cable.
Connect each end of the leader cable as follows:
1
With the screws of the terminal block connector on the LD1500 facing up, connect the four
stripped, bare wires of the leader cable to the terminals in this order, from left to right:
white, black, green, red. Tighten the screws to secure the ends of the leader cable, and plug
the connector into TB2. Make sure the wires, from left to right, are in the white-black-
green-red order.
Note
If the terminal connector is removed from the end of the cable, make sure the wires are in
white-black-green-red order when the connector is reapplied.
2
Unscrew the end-of-line (EOL) terminator from the other end of the leader cable.
3
Attach the first length of leak detection cable (sensing cable) to the leader cable.
Figure 3.1 SeaHawk Sensing Cable