5.2. Packet

Communications for the LD1500

5.2.1 Function 03: Read Output Registers

To read the LD1500 parameter values, the master must send a Read Output Registers request

packet.The Read Output Registers request packet specifies a start register and the number of

registers to read. The start register is numbered from zero (40001 = zero, 40002 = one, etc).

Table 5.2 Read Output Registers Packet Structure

Read Registers Request Packet

Read Registers Response Packet

Slave Address (1 byte)

Slave Address (1 byte)

03 (Function code) (1 byte)

03 (Function code) (1 byte)

Start Register (2 bytes)

Byte count (1 byte)

# of registers to read (2 bytes)

First register (2 bytes)

CRC Checksum (2 bytes)

Second register (2 bytes)

CRC Checksum (2 bytes)

Table 5.3 Output Registers

Register

Name

Description

Range, Units

Range

40001

Leak Threshold

Trip current for leak alarm

25-295

μ

Amps

0-65535

40002

Contamination Threshold

Trip current for

contamination alarm

20-295

μ

Amps

0-65535

40003

Spare

0-65535

40004

Spare

0-65535

40005

Spare

0-65535

40006

Spare

0-65535

40007

Spare

0-65535

40008

Spare

0-65535

40009

Spare

0-65535

40010

Spare

0-65535

40011

Spare

0-65535

40012

Spare

0-65535

40013

Spare

0-65535

40014

Spare

0-65535

40015

Spare

0-65535

40016

Leak Alarm Delay

Leak Alarm Delay

5-995 seconds

0-65535

40017

Contamination Alarm Delay

Contamination Alarm Delay

5-995 seconds

0-65535