Page 39: Table 5.2, Read output registers packet structure, Table 5.3, Output registers, S. see table
rletech.com
LD1500 User Guide
39
5
Modbus Communication
5.2. Packet
Communications for the LD1500
5.2.1 Function 03: Read Output Registers
To read the LD1500 parameter values, the master must send a Read Output Registers request
packet.The Read Output Registers request packet specifies a start register and the number of
registers to read. The start register is numbered from zero (40001 = zero, 40002 = one, etc).
Table 5.2 Read Output Registers Packet Structure
Read Registers Request Packet
Read Registers Response Packet
Slave Address (1 byte)
Slave Address (1 byte)
03 (Function code) (1 byte)
03 (Function code) (1 byte)
Start Register (2 bytes)
Byte count (1 byte)
# of registers to read (2 bytes)
First register (2 bytes)
CRC Checksum (2 bytes)
Second register (2 bytes)
…
CRC Checksum (2 bytes)
Table 5.3 Output Registers
Register
Name
Description
Range, Units
Range
40001
Leak Threshold
Trip current for leak alarm
25-295
μ
Amps
0-65535
40002
Contamination Threshold
Trip current for
contamination alarm
20-295
μ
Amps
0-65535
40003
Spare
0-65535
40004
Spare
0-65535
40005
Spare
0-65535
40006
Spare
0-65535
40007
Spare
0-65535
40008
Spare
0-65535
40009
Spare
0-65535
40010
Spare
0-65535
40011
Spare
0-65535
40012
Spare
0-65535
40013
Spare
0-65535
40014
Spare
0-65535
40015
Spare
0-65535
40016
Leak Alarm Delay
Leak Alarm Delay
5-995 seconds
0-65535
40017
Contamination Alarm Delay
Contamination Alarm Delay
5-995 seconds
0-65535