LD1500 User Guide

35

4

Web Interface

4.3.10 BACnet Alarm

The BACnet Alarm Configuration page allows the user to configure the BACnet alarm

settings.

Figure 4.14 BACnet Alarm

Option

Description

Recipient #1 IP

Address

When there is a BACnet alarm, a message will be sent to this

address.

PID

BACnet Process Identifier - Additional information that can be sent

with an alarm to indicate what the alarm recipient should do once

the alarm is received.

Notification Type

Select unconfirmed or confirmed. If you select confirmed, the

recipient will be required to acknowledge the alarm.

Notification Class

A list of devices to be informed if an event enrollment object

determines that a warning or alarm message needs to be sent.

Notification Priority

Designate a priority to controls where conflicting control situations

may occur.

Leak Detected Alarms Select analog or binary.

APDU Timeout

The amount of time in seconds between retransmissions of an

APDU requiring acknowledgement for which no acknowledgement

has been received.

Number of APDU

retries

The maximum number of times an APDU is retransmitted.

Table 4.7 BACnet Alarm Configuration Options