beautypg.com

Product overview, Description, Operation – RLE LD1500 V.3.1 User Manual

Page 11: Description operation, Roduct, Verview

background image

rletech.com

LD1500 User Guide

11

C

H A P T E R

C

HAPTER

0

P

RODUCT

O

VERVIEW

1.1. Description

The LD1500 is a complete monitoring system that detects and reports the presence of water

and other conductive liquids. The LD1500 couples SeaHawk Leak Detection Cable (sensing

cable) with an advanced control panel. Each LD1500 monitors up to 1,500 feet (457.2m) of

sensing cable. When a conductive liquid comes in contact with the sensing cable, an Alarm

LED is illuminated red on the front panel, the distance to the leak is shown on the LD1500’s

web page, and alarm notifications are distributed via user-configurable Modbus (EIA-485

RTU or TCP/IP), BACnet (EIA-485 MS/TP or IP), or SNMP.

1.2. Operation

When the LD1500's analog circuitry measures a current in excess of the user-defined leak

threshold, the unit's microprocessor computes the distance to the leak. The unit then

annunciates the leak and logs the alarm in its event log. The LD1500 provides a webpage

interface to allow users to get updates on the unit's conditions via the Internet or local area

network. The LD1500 also provides Modbus and BACnet outputs via EIA-485, twisted-pair

wire or TCP/IP.

Note The LD1500 produces an alarm in the following conditions:

Leak detected

Cable break (or cable fault)

Cable contamination

Loss of communications

The LD1500 is a supervised system; it continually monitors the cable for continuity. A cable

break or excess contamination of the cable causes an Alarm indication and notification.