beautypg.com

Modbus communication, Implementation basics, 1 modes of transmission – RLE LD1500 V.3.1 User Manual

Page 37: 1 slave address field, Modes of transmission, Slave address field, Odbus, Ommunication

background image

rletech.com

LD1500 User Guide

37

C

H A P T E R

C

HAPTER

0

M

ODBUS

C

OMMUNICATION

This document describes the Modbus communications protocol as supported by the LD1500

Distance Read System. It includes details and information on how to configure the LD1500 for

communications via Modbus network.

5.1. Implementation

Basics

The LD1500 is capable of communicating via the half-duplex EIA-485 serial communication

standard. The LD1500 is configured to act as a slave device on a common network. The EIA-

485 medium allows for multiple devices on a multi-drop network. The LD1500 is a slave only

device and will never initiate a communications sequence.

5.1.1 Modes of Transmission

The Modbus protocol uses ASCII and RTU modes of transmission. The LD1500 supports only

the RTU mode of transmission, with 8 data bits, no parity and 1 stop bit. Every Modbus packet

consists of four fields:

Slave Address Field

Function Field

Data Field

Error Check Field (Checksum)

5.1.1.1 Slave

Address

Field

The slave address field is one byte in length and identifies the slave device involved in the

transaction. The valid address range is between 1 and 254. The slave address is set from the

Modbus/EIA-485 Configuration web page (see 4.3.7, “EIA-485/Modbus/N2” on page 32).