LD1500 User Guide

800.518.1519

5

Modbus Communication

5.2.2 Function 04: Read Input Registers

To read the LD1500 input values, the master must send a Read Input Registers request packet.

The Read Input Registers request packet specifies a start register and the number of registers

to read. The start register is numbered from zero (30001 = zero, 30002 = one, etc).

Table 5.4 Read Input Registers Packet Structure

Read Registers Request Packet

Read Registers Response Packet

Slave Address (1 byte)

Slave Address (1 byte)

04 (Function code) (1 byte)

04 (Function code) (1 byte)

Start Register (2 bytes)

Byte count (1 byte)

# of registers to read (2 bytes)

First register (2 bytes)

CRC Checksum (2 bytes)

Second register (2 bytes)

CRC Checksum (2 bytes)

Table 5.5 Input Registers

Register

Name

Description

Units

Range

30001

Status

Bit Level Status

None

0-65535

30002

Leak Distance

Location of Leak

Ft/Meters

0-65535

30003

Units

Unit of Measure

1=Ft 0=Meters

0-65535

30004

Leak Current

Leakage current on cable

μ

Amps

0-65535

30005

Cable Length

Installed Cable Length

Ft/Meters

0-65535

30006

Loop1 Res

Resistance of cable

Ohms

0-65535

30007

Loop2 Res

Resistance of cable

Ohms

0-65535

30008

Res/Ft

Resistance of cable

Ohms x1000

0-65535

30009

Version

Firmware version

xx.xx X 100

0-65535

Table 5.6 Status Flags (Register 30001)

Bit

Description

00

1 = Leak is Detected

01

1 = Cable Break Alarm

02

1 = Contamination is detected

03

1 = Summary Alarm

04-15

Spare