Modbus Communication

4.4.

Calibrate Cable Length via Modbus

The length of sensing cable connected to the SeaHawk 10K can be calibrated through a

Modbus-enabled system. This helps fine-tune a distance-read leak detection system. If no

alarms are present, follow these steps to calibrate and test the system:

1

Set the SW1 DIP switches for the correct cable resistance per foot, as follows:

Figure 4.1 DIP Switch Settings for Ohms/Foot

2

Press the Test/Reset button on the controller once to verify the cable’s amperage reading.

Calibration cannot be performed if the current is above 15

μA.

Different sensing cables are cleaned in different ways. The following cleaning instructions

apply to RLE’s orange sensing cable ONLY! If you have questions regarding the care and

maintenance of your sensing cable, please consult the cable’s data sheet or contact the

manufacturer.

If the cable is new and the current is higher than 1

μA, clean the cable. Isopropyl alcohol

removes any contamination that might have been introduced to the cable during installation.

If the cable is older and the amperage reading is above 15

μA, clean the cable. A mild dish

detergent solution removes most dirt. Isopropyl alcohol is also an effective cable cleaner.

3

Sensing cable has a resistance - for example, RLE’s orange cable has a resistance of 2.8

ohms per foot. A system's actual resistance will rarely be exactly 2.8 ohms per foot, but it

will be close - each individual cable or system will vary a very small bit from that 2.8 ohms

per foot value. If you know the exact resistance of your cable, you can fine-tune your

system for a more precise distance reading. The formula for calculating this value - and

more specific directions for using the formula - are as follows:

Figure 4.2 Formula for Calculating Exact Cable Resistance

4

Read the Leg 1 and Leg 2 Resistance values in Modbus registers 30006 and 30007. Ensure

that the reading are similar - within 2% of each other. This helps rule out any major cable

problems before calibration begins. Record the resistance reading from Leg 2, Modbus

register 30007.

Leg2 Resistance (Modbus register 30007)

(Modbus register 40008)

Resistance per foot

in milliohms/foot

Total Feet of Cable Installed on the System

X

1000