2.6.2 Secure Sensing Cable to the Floor

Secure the sensing cable to the floor with either J-clips (RLE part #JC), or one of the other

approved methods shown in

Figure 2.17

. Available from RLE and designed specifically for

use with sensing cable, J-clips are the manufacturer's recommended installation method.

To avoid contaminating the cable, clean the entire floor as much as possible. Use isopropyl

alcohol to clean the spots on the floor where J-clips will be placed.

Place one J-clip every 5 to 6 feet (1.52 to 1.83m) along the length of the sensing cable and

one at each turn of the cable. Use more J-clips if a tighter configuration is required.

If the cable is installed over an obstruction, clip the cable on both sides, as close to the

obstruction as possible.

The J-clip’s adhesive backing does not work well on porous concrete floors. RLE

recommends using a drop of silicone or another nonconductive adhesive to help secure the

J-clip to the floor.

IMPORTANT

Do not install the cable directly in front of an air conditioner. Allow a minimum of 4 to 6 feet

(1.22 to 1.83m) between the unit and the cable. If the cable is too close to the air conditioning

unit’s air stream, the moisture from the humidifier may cause false leak readings. If the cable

must be installed in front of an air conditioning unit, place the J-clips 3 feet (0.91m) apart.

.

Figure 2.17

Secure the Cable