Operation

3.2. Manage

Alarms

General Guidelines

1

If the audible alarm sounds, briefly press the Test/Reset button to silence it.

2

Look at the display, or read the appropriate Modbus register, to determine the type of alarm

and the distance to the leak, contamination, or cable break.

3

If you have a leak detection reference map, cross-reference the distance with the map.

4

Fix the problem (fix the leak, then dry the area and the section of cable involved in the leak;

replace broken cable; clean contaminated cable).

Contamination Alarm Guidelines

If the cable is in a contamination alarm state, check the following:

Verify that the cable is at least 4

feet (1.22m)

away from any air conditioning unit.

If there is dirt, grit, or grime on the cable, clean the cable with isopropyl alcohol and a clean

rag.

If the cable is in a high traffic area, move it or install a cable protector over it.