RLE 10K V.2.5.a User Manual
Page 32

32
SeaHawk 10K User Guide
800.518.1519
4
Modbus Communication
40006
Reset Alarm
Resets the
SeaHawk 10K after an
alarm state.
Alternatively, press and
hold the front panel’s
Test/Reset button for 3
seconds.
0 = Disabled (do not
reset alarm)
1 = Enabled (reset
alarm)
Default: 0 (Disabled)
0-65535
40007
Sample Size
Number of samples
taken to calculate the
leak location
0 = Set to default value
4 = Minimum
25 = Maximum
Default: 12
0-65535
40008
Resistance per Foot
Milliohms of resistance
of installed leak
detection cable. This
value is set here and can
also be read through
register 30008.
2000 – 3500 Milliohms/
foot*
or
3500 – 4240 Milliohms/
foot*
*to convert this value to
Ohms/foot, divide the
number by 1000
0-65535
40009
AC Rejection Frequency
Used by ADC to reject
AC powerline
frequencies. Needed
only if the SeaHawk10K
is running on 24VAC
power.
0 = 60Hz
1 = 50Hz
Default: 1 (50Hz)
0-65535
40010
Spare
Not used.
0-65535
40011
Spare
Not used.
0-65535
40012
Spare
Not used.
0-65535
40013
Spare
Not used.
0-65535
40014
Spare
Not used.
0-65535
40015
Spare
Not used.
0-65535
40016
Leak Alarm Delay
Amount of time that
passes between leak
detection and alarm
notification.
5 – 990 seconds
Default: 10 seconds
0-65535
40017
Contamination Alarm
Delay
Amount of time that
passes between cable
contamination detection
and alarm notification.
5 – 990 seconds
Default: 120 seconds
0-65535
Register
Name
Description
Units
Range
Table 4.3
Output Registers